Power supply voltage: | - 19V ÷ 50V DC
- 16V ÷ 35V AC
- 85 ÷ 260V AC/DC
|
Power consumption: | typical 7 VA; max. 12 VA |
Display: | lit, graphic LCD, 128 x 64 points, with backlight |
Measuring inputs: | 8, Pt100; Pt500; Pt1000 (2 and 3-conductor connection) or 0/4-20 mA inputs; common earthing Digital input: 1 input 24V DC |
Measuring range: | ± 9999 + decimal point (current inputs); -100°C +600°C (RTD inputs) with resolution 0,1°C |
Outputs: | 2 electronic relays (ER1, ER2) with max. load 24V AC (35V DC) / 200 mA |
Sensors supply: | 24 V DC±5% / 200 mA, not separated from measuring inputs |
Communication interface: | RS-485 (MODBUS RTU) or USB Host port, galvanically separated |
Transmission speed: | 1200 - 115200 bit/sec. |
Memory capacity: | - 2 MB (0,5 milion data recordings)
- 8 MB (above 2 milion data recordings) in version with USB Host
|
Type of protection: | version without USB: - IP 40 (front side)
- IP 65 (front side when an additional frame is installed)
version with USB: - IP 20
- IP 42 (when transparent door with security key type STD-99 is installed)
|
Working temperature: | 0°C ÷ +60°C |
Storage temperature: | -10°C ÷ +70°C |
Case: | board |
Case material: | NORYL - GFN2S E1 |
Case dimensions: | 96 x 96 x 100 mm |
Panel cut-out dimensions: | 90,5 x 90,5 mm |
Installation depth: | min. 102 mm |
Board thickness: | max. 5 mm |